Trasmission

GUARANTEED TECHNICAL PERTICULARS

VOLTAGE RATING :

INSULATOR TYPE :

MINIMUM FAILING LOAD :

CREEPAGE FACTOR :

STANDARD :

66-72.5kV/110-145kV/220-245kV/400kV

BALL & SOCKET (B&S)/ TONGUE & CLEVIS (T&C)/ EYE & TONGUE (E&T)/ BALL & HOOK (B&H)

70KN/ 90KN/ 120KN/160KN

31mm/kV

IEC 61109 / IEC 62217

GUARANTEED TECHNICAL PERTICULARS

Nominal Voltage

Highest Voltage

System Frequency

Creepage Distance

Power Frequency Withstand Voltage (Dry)

Power Frequency Withstand Voltage (Wet)

: 66 kV

: 72.5 kV

: 50/60 Hz

: 2248 mm

: 160 kV (rms) 

: 140 kV (rms) 

:110kV

:145kV

:50/60 Hz

:4495 mm

:325 kV (rms)

:275 kV (rms)

Nominal Voltage

Highest Voltage

System Frequency

Creepage Distance

Power Frequency Withstand Voltage (Dry)

Power Frequency Withstand Voltage (Wet)

:220kV

:245kV

:50/60 Hz

:7595mm

:525 kV (rms)

:460 kV (rms)

:400 kV

:420 kV

:50/60 Hz

:13020 mm

:700 kV (rms)

:650 kV (rms)